EtherCAT端子模块

EL1889 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, ground switching

The EL1889 digital input terminal acquires the binary 24 V control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit

联系电话
188-2320-5277

The EL1889 digital input terminal acquires the binary 24 V control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The EtherCAT Terminal has 16 channels, whose signal states are indicated by LEDs. The power contacts are connected through. With the EL1889, the reference ground for all inputs is the 24 V power contact.


Special features:


·  ground switching

·  no bouncing due to mechanical switches thanks to 3 ms input filter

·  tool-free connection by direct plug-in technique for solid wire conductors

·  space-saving use in the control cabinet

·  direct connection of multi-channel sensors in 1-wire connection technology in the smallest space


Product status:

regular delivery


Product information

·  Technical data
·  Accessories
·  Documentation and downloads
·  Beckhoff Information System
·  Further information
·  Related products
·  Technical data
·  Housing data

To top

Technical data

EL1889

Connection technology

1-wire

Number of inputs

16

Nominal voltage

24 V DC (-15 %/+20 %)

“0” signal voltage

18…30 V

“1” signal voltage

0…7 V

Input current

typ. 3 mA

Input filter

typ. 3.0 ms

Distributed clocks

Current consumption power contacts

typ. 35 mA

Current consumption E-bus

typ. 110 mA

Electrical isolation

500 V (E-bus/field potential)

Configuration

no address or configuration setting

Weight

approx. 55 g

Operating/storage temperature

-25…+60 °C/-40…+85 °C

Relative humidity

95 %, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6/EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2/EN 61000-6-4

Protect. rating/installation pos.

IP20/variable (see documentation)

Approvals/markings

CE, UL, ATEX, IECEx

Ex marking


ATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc


Housing data

EL-12-16pin

Design form

HD (High Density) housing with signal LEDs

Material

polycarbonate

Dimensions (W x H x D)

12 mm x 100 mm x 68 mm

Installation

on 35 mm DIN rail, conforming to EN 60715 with lock

Side by side mounting by means of

double slot and key connection

Marking

labeling of the BZxxx series

Wiring

solid conductors (e): direct plug-in technique; fine-stranded 

conductors (f) and ferrule (a): spring actuation by screwdriver

Connection cross-section

s*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²

Connection cross-section AWG

s*: AWG 28…16,
st*: AWG 22…16,
f*: AWG 26…19

Stripping length

8…9 mm

Current load power contacts

Imax: 10 A

留言咨询